201-55 Alexander Street, Vancouver, BC V6A 1B2
RealDream Contracting logo
Permits & Regulations

STC 43, ASTC 40, or the Recipe: How BC Code Actually Rates a Suite Wall

Sound is the complaint we hear most often after a suite is finished, and almost always from the owner upstairs rather than the tenant below. The odd part is that the code question behind it is simpler than people expect. For a secondary suite the BC Building Code gives you three separate ways to comply, and one of them is a construction recipe that requires no test report, no rating number, and no consultant. Most homeowners never learn that path exists, so they either overbuild or, more commonly, build something that fails on site for reasons the rating number would never have caught anyway.

By Nima Gerani, Founder, RealDream Contracting
September 28, 2026 12 min read

The short answer

BC Building Code Sentence 9.11.1.1.(2) lets a secondary suite meet sound separation three ways: a prescriptive recipe of sound-absorbing material in joist and stud spaces, resilient channel on one side, and 12.7 mm gypsum board, with no rating number required; or a tested STC rating of at least 43; or an ASTC rating of at least 40 for the assembly plus adjoining constructions. Suites between other dwelling units face a higher bar of ASTC 47 or STC 50.

Note: Code editions and municipal alternate compliance rules change. Confirm the current requirements and which edition applies to your project with the building department at the City or District of North Vancouver before you frame anything.

The general rule, and why a suite gets an easier one

Start with the baseline that applies between any two dwelling units. Sentence 9.11.1.1.(1) requires that a dwelling unit be separated from every other space in the building where noise may be generated, by one of two things: a separating assembly and its adjoining constructions together providing an apparent sound transmission class (ASTC) rating of not less than 47, or a separating assembly providing a sound transmission class (STC) rating of not less than 50 with adjoining constructions conforming to Article 9.11.1.4.

Those two numbers describe the same real-world result by different methods. STC measures the assembly on its own, in a laboratory, where sound can only pass through the wall. ASTC measures the finished building, where sound also travels around the wall through the floor and the side walls. That extra route is called flanking. Because ASTC counts the flanking noise and STC does not, the ASTC threshold sits lower for the same outcome: 47 rather than 50.

Then comes the part that matters here. Sentence 9.11.1.1.(2) sets a different, lower standard specifically for secondary suites, and the code explains its own reasoning in Note A-9.11.1.1.(2). A reduced level of performance is acceptable in a secondary suite because the occupants of the house are only affected by the sound of one other unit, and in many cases it is the owner of the house who decides on the desired level of protection.

That is worth reading carefully, because it hands the decision back to you. The code sets the floor. Whether you build to the floor or well above it is a choice you make once, at framing, and cannot revisit later without opening the ceiling again.

The three compliance paths for a secondary suite

Sentence 9.11.1.1.(2) gives three options, and you only need to satisfy one. They are not equivalent in effort, in cost, or in what they demand from the design team.

Path (a) is prescriptive. Build the assembly this way and it complies, with no rating attached: joist spaces filled with sound-absorbing material of not less than 150 mm nominal thickness, stud spaces filled with sound-absorbing material, a resilient channel on one side of the separation spaced at 400 or 600 mm on centre, and not less than 12.7 mm thick gypsum board on ceilings and on both sides of walls. No test report, no consultant, no number to prove.

Path (b) is a tested performance number: construction providing an STC rating of not less than 43. This is where the assembly tables come in, since the code publishes typical STC values for standard assemblies and you can select one that meets or beats 43.

Path (c) is the whole-system number: a separating assembly and adjoining constructions together providing an ASTC rating of not less than 40. This one accounts for flanking, which makes it the most honest description of what an occupant will actually hear, and also the most work to demonstrate.

For a house with a suite, path (a) is usually the practical answer. A building official can verify it by looking at the framing and reading a product label. Paths (b) and (c) both require someone to establish a rating, and path (c) requires modelling the whole junction assembly, which on a typical basement suite is a consultant's fee attached to a result the recipe would have delivered anyway.

The three secondary suite sound separation paths, BC Building Code 9.11.1.1.(2)
Path What the code requires What you have to prove Where it fits
(a) Prescriptive recipe 150 mm nominal sound-absorbing material in joist spaces, absorptive material in stud spaces, resilient channel one side at 400 or 600 mm o.c., 12.7 mm gypsum board on ceilings and both wall faces Nothing. No rating number is required. Compliance is by construction Almost every basement suite. Verified by inspection of the framing
(b) STC 43 Construction providing a sound transmission class rating of not less than 43 A rating for the assembly, typically by selecting a listed assembly from the code tables Where the assembly departs from the recipe, for example no resilient channel because of ceiling height
(c) ASTC 40 Separating assembly plus adjoining constructions together providing an apparent sound transmission class rating of not less than 40 A whole-system rating that accounts for flanking through floors and side walls Where a designer is already modelling the building, or where the owner wants a number tied to real performance

The assemblies, and the number that looks backwards

Table 9.10.3.1.-A carries a column titled Typical Sound Transmission Class alongside the fire-resistance data, so the same table that tells you an assembly's fire rating also tells you roughly what it does for sound. A handful of the wall assemblies are worth knowing by name.

Look at W4a and W4b. Same studs, same absorptive material, same layers of gypsum board, same resilient channel. The only difference is stud spacing: 400 mm on centre for W4a and 600 mm for W4b. And the wider spacing rates higher, 54 against 51.

That surprises people, so here is the reason. Every stud is a rigid piece of wood touching the gypsum board on both sides of the wall. Sound travels through it directly, bypassing the insulation in the cavity. Fewer studs means fewer of those rigid paths, so the wall performs better. The same logic explains why the resilient channel matters so much: it exists to break that contact on one side entirely.

Note also where W3c sits. Studs at 400 or 600 on centre with 12.7 mm Type X gypsum board rates STC 43, which lands exactly on the secondary suite minimum under path (b). It clears the bar with nothing to spare, which means any site error, any unsealed penetration, any back-to-back outlet, and the real performance drops below what you designed for.

Wall assemblies and their typical STC, from BC Building Code Table 9.10.3.1.-A
Assembly Construction Typical STC
W3c Studs at 400 or 600 mm o.c., 12.7 mm Type X gypsum board 43
W4a 38x89 studs at 400 mm o.c., 89 mm absorptive material, resilient metal channel one side, 2 layers gypsum board channel side and 1 layer other side, 15.9 mm Type X 51
W4b As W4a but studs at 600 mm o.c. 54
W5b 38x89 studs at 600 mm o.c., 89 mm absorptive material, resilient channel one side, 1 layer channel side and 2 layers other side, 15.9 mm Type X 54
W6a 38x89 studs, 89 mm absorptive material, resilient channels at 400 mm o.c., 2 layers 15.9 mm Type X each side 55

Where the ratings come from, and what they do not include

Article 9.11.1.2 sets out how the ratings are determined. STC is measured to ASTM E413 using sound transmission loss values from ASTM E90, a laboratory method. ASTC uses the same ASTM E413 classification but with field measurements to ASTM E336. Article 9.11.1.3 covers compliance with those required ratings, and Article 9.11.1.4 covers adjoining constructions, including Table 9.11.1.4 for floor treatments.

That last article is the one people skip, and the code itself flags the risk. Note A-9.11.1.3.(2)(b) says that selecting an appropriate separating assembly is only one part of the solution, and that to fully address the sound performance of the whole system, flanking assemblies must be connected to the separating assembly in accordance with Article 9.11.1.4.

In plain terms: a wall rated STC 54 does not deliver STC 54 if sound walks around it through the subfloor and the side walls. The rating describes a panel tested in isolation. Your basement is not isolated.

One more limitation worth naming. STC and ASTC describe airborne sound: voices, music, television. Footsteps are impact sound, which travels as vibration through the structure, and neither number describes it. On the jobs we run, footsteps overhead are the complaint that arrives most often after move-in, and it arrives from suites that met the code requirement exactly as written. Floor coverings, underlay, and how the ceiling is hung are where that gets addressed.

What actually ruins the separation on site

Everything above is design. Here is what we see fail during construction, and none of it shows up on a rating table.

The single most common error on a suite job is resilient channel installed wrong. The channel works by holding the gypsum board away from the framing so vibration cannot pass straight through. Drive a screw through the board, through the channel, and into the stud behind it, and you have bolted the two together again. The channel is now a decorative strip of metal. It does nothing at all, and nothing about the finished wall looks different, so it is never caught until the tenant moves in.

The second is back-to-back electrical boxes in the same stud cavity. Two boxes cut opposite each other leave a thin gypsum membrane between two rooms, and both faces of the assembly are now open into the same air space. Offset them by at least one stud bay.

After that it is penetrations, in every form. Plumbing stacks that pass through the separation, ducts crossing it, pot lights cut into the ceiling, unsealed gaps where the top plate meets the floor above. Air paths are sound paths. A gap you can slide a business card through will carry conversation.

And then rigid contact at the edges: where the new ceiling assembly ties into the existing side walls, where the wall meets the floor slab. Those junctions are the flanking paths that Article 9.11.1.4 exists to control, and on a retrofit in an existing house they are usually the hardest part of the job.

  • Resilient channel screwed through into the stud behind it, which cancels it completely
  • Back-to-back electrical boxes sharing one stud cavity
  • Plumbing stacks and vent pipes passing through the separation unsealed
  • Ducts crossing between the two units
  • Pot lights cut through a rated ceiling assembly
  • Unsealed gaps at the top plate, the floor edge, and around penetrations
  • New assembly tied rigidly into existing side walls, creating a flanking path

The ductwork problem, which is two problems at once

A house with a suite very often ends up with one furnace serving both units, because separating the systems is expensive and the existing equipment is sitting right there. The code has something to say about that.

Sentence 9.32.3.2.(4) states that in a house with a secondary suite, where a heating or ventilation system serves more than a single dwelling unit, the system must be designed and installed to prevent the circulation of smoke upon a signal from a duct-type smoke detector. That is a life safety requirement, and it is checked.

The sound consequence rides along with it. A duct that runs from the upstairs return, through the basement, and into the suite is a continuous air path between two units, and air paths carry sound. You can build a ceiling assembly to STC 55 and still hear a conversation clearly through a shared return, because the sound never touched the ceiling. It went around through the sheet metal.

Where the budget allows, fully separate systems solve both the smoke requirement and the sound problem in one move, and they simplify the utility question if the suite is ever rented separately. Where it does not, the ducts need lined sections, offsets, and proper sealing at every point they cross the separation, and that work has to be planned before the ceiling closes.

Adding a suite to an existing house is a different rulebook

New construction and retrofit are treated differently, and this catches people who read the code straight through without noticing.

Table 1.1.1.1.(6) provides alternate compliance requirements for adding a secondary suite to an existing house. Several standards are relaxed, including ceiling heights, which drop from 2.1 m to 1.95 m, along with doorway sizes, fire ratings, and sound requirements. That relaxation is the difference between a suite being possible and impossible in a lot of older North Shore basements, where the joists sit lower than anything built today would allow.

Which set applies to your project is a determination the building department makes, based on the age of the house, the scope of what you are doing, and how the municipality reads it. The City of North Vancouver and the District of North Vancouver are separate jurisdictions with their own building departments, and this is a question to ask at the counter early, before the design is fixed. On the projects we run, that single conversation reshapes the ceiling detail more often than any other.

The one thing we would not do is design down to the relaxed minimum just because it is available. Ceiling height you cannot recover. Sound separation you can improve later only by demolishing the ceiling you just paid for.

What we would build, and why

Given the choice on a basement suite, follow the prescriptive recipe in path (a) and then spend a little more on the things the recipe does not cover.

The recipe is the practical path because it is verifiable. A building official can see 150 mm of sound-absorbing material in the joist spaces, see the resilient channel spacing, and read the thickness off the gypsum board. Nobody has to trust a report. And it is genuinely good construction: absorptive material in the cavity, a broken contact path, and mass on both faces are the three things that make a separation work.

The extras worth adding on top are cheap at framing stage and expensive afterwards. Seal every penetration properly with acoustic sealant rather than expanding foam. Offset the electrical boxes. Keep the ducts on separate systems or line and seal them where they cross. Brief the drywall crew specifically about the resilient channel screw length before they start, and check the first wall yourself.

For an owner living directly above the suite, going past the minimum is the decision the code note anticipated. Two layers of gypsum board instead of one costs very little relative to the whole project, and W6a at STC 55 exists in the same table as the assemblies that scrape by at 43. The gap between them is a few hundred dollars in material and the willingness to decide before the ceiling goes up.

Sources

Frequently asked questions

What STC rating does a secondary suite need in BC?

A secondary suite needs an STC rating of not less than 43 if you take the tested performance path under BC Building Code Sentence 9.11.1.1.(2)(b). But that is only one of three options. You can instead follow the prescriptive recipe in 9.11.1.1.(2)(a), which requires no rating number at all, or demonstrate an ASTC rating of not less than 40 under 9.11.1.1.(2)(c) for the assembly plus adjoining constructions.

Why does a secondary suite have a lower sound requirement than an apartment?

The BC Building Code explains this itself in Note A-9.11.1.1.(2). A reduced level of performance is acceptable in a secondary suite because the occupants of the house are only affected by the sound of one other unit, and in many cases it is the owner of the house who decides on the desired level of protection. Between dwelling units generally, Sentence 9.11.1.1.(1) requires ASTC 47 or STC 50, well above the suite thresholds of ASTC 40 or STC 43.

What is the difference between STC and ASTC?

STC rates the separating assembly on its own, measured in a laboratory to ASTM E413 using transmission loss values from ASTM E90. ASTC rates the assembly together with its adjoining constructions using field measurements to ASTM E336, so it captures flanking sound that travels around the wall through floors and side walls. Because ASTC counts that extra path, its required number is lower for the same real-world result: 47 against 50 between dwelling units, and 40 against 43 for a secondary suite.

Do I need a sound test to get my North Vancouver suite approved?

Not if you build to the prescriptive recipe. BC Building Code 9.11.1.1.(2)(a) lets a secondary suite comply through construction alone: 150 mm nominal sound-absorbing material in joist spaces, absorptive material in stud spaces, resilient channel on one side at 400 or 600 mm on centre, and 12.7 mm gypsum board on ceilings and both sides of walls. No rating and no test report is required. Confirm the approach with the City or District of North Vancouver building department, since they are separate jurisdictions with their own review.

Why do studs at 600 mm on centre rate higher than 400 mm?

Because each stud is a rigid path that carries sound straight through the wall, bypassing the cavity insulation. Fewer studs means fewer of those paths. In BC Building Code Table 9.10.3.1.-A, assembly W4a with studs at 400 mm on centre rates STC 51, and W4b, identical except for studs at 600 mm on centre, rates STC 54. The same logic explains the resilient channel, which exists to break that rigid contact on one side entirely.

Will my suite ceiling stop footstep noise from upstairs?

Not necessarily, because STC and ASTC only describe airborne sound such as voices, music, and television. Footsteps are impact sound, which travels as vibration through the structure, and neither rating measures it. On the projects we run, footsteps overhead are the most frequent complaint after a tenant moves in, and they come from suites that met the code sound requirement exactly. Floor coverings, underlay, and how the ceiling is hung are where impact noise is addressed.

What is the most common soundproofing mistake on a basement suite job?

Resilient channel installed with screws driven through into the stud behind it. The channel works only by holding the gypsum board away from the framing so vibration cannot pass through directly. Once a screw connects them, the channel does nothing at all, and the finished wall looks identical, so the error is never caught until someone is living there. Brief the drywall crew on screw length before they start and check the first wall.

Do the sound rules change for a suite in an older Lynn Valley or Upper Lonsdale house?

There is a separate path for existing buildings. Table 1.1.1.1.(6) of the BC Building Code provides alternate compliance requirements for adding a secondary suite to an existing house, relaxing ceiling heights from 2.1 m to 1.95 m along with doorway sizes, fire ratings, and sound requirements. That matters in older North Shore houses where basement joists sit low. Which set applies to your project is determined by the building department, so ask at the counter before the design is fixed.

Can the suite share a furnace with the main house?

It can, with a condition. BC Building Code Sentence 9.32.3.2.(4) states that in a house with a secondary suite, where a heating or ventilation system serves more than a single dwelling unit, the system must be designed and installed to prevent the circulation of smoke upon a signal from a duct-type smoke detector. A shared duct is also a continuous air path between the units, which carries sound around the ceiling assembly entirely, so separate systems solve two problems at once where the budget allows.

Does an STC 43 wall assembly actually deliver STC 43 in my basement?

Usually less, because the rating describes a panel tested in isolation. Note A-9.11.1.3.(2)(b) of the BC Building Code states that selecting an appropriate separating assembly is only one part of the solution, and that flanking assemblies must be connected to the separating assembly in accordance with Article 9.11.1.4 to address the whole system. Sound travelling around the wall through the subfloor and side walls is not captured in the STC number.

Why offset electrical boxes in a suite separation wall?

Two boxes cut back to back in the same stud cavity leave only a thin gypsum membrane between the two units, and both faces of the assembly open into the same air space. Sound passes through almost unimpeded regardless of what the assembly is rated. Offsetting them by at least one stud bay removes the shared cavity. It costs nothing at rough-in and cannot be fixed afterwards without opening the wall.

Is it worth building above the code minimum for a suite?

For an owner living directly above the suite, yes, and the code note anticipates exactly that choice by saying the owner decides on the desired level of protection. Assembly W3c rates STC 43, landing exactly on the minimum with nothing to spare, while W6a in the same table rates STC 55. The difference is largely a second layer of gypsum board, which is a small share of a basement suite budget and cannot be added later without demolition.

Related service

Secondary suites

See how we handle secondary suites projects across the North Shore.

Learn about secondary suites

Free quote

Get a project estimate

Share a few details and we'll respond within one business day.

Ready to build?

Talk to RealDream Contracting.

Call (604) 401-4849, send an inquiry, or book a consultation to discuss your project on the North Shore.

RealDream × Realtors

Let's build something together.

Leave your details. Let's talk about working together.

An introduction starts the conversation. Partnership terms are agreed together.

Prefer a conversation? (604) 401-4849